Watts to Amps Calculator
Convert watts to amps, or amps back to watts, for DC, single-phase AC, or three-phase circuits, with power factor and a quick amperage reference table.
Published
Last updated
How the Watts to Amps Calculator Formula Works
Converting watts to amps always comes down to Watt's law, current equals power divided by voltage, but which exact version of that equation applies depends on the circuit. A direct-current circuit uses the plain version: divide watts by volts and you have amps. An alternating-current single-phase circuit, the kind running most household outlets and appliances, adds one more factor: power factor (PF), a number between 0 and 1 that accounts for how much of the delivered power actually does useful work versus how much gets tied up in the magnetic fields of motors, compressors, and transformers. Divide watts by the product of volts and power factor, and you get the real current the circuit draws.
Three-phase circuits split further depending on which voltage you measured. If you took the voltage between two hot legs (line-to-line, the number stamped on most three-phase equipment nameplates), the formula divides by the square root of 3, about 1.732, times volts times power factor. If you measured from one hot leg to neutral instead (line-to-neutral, used inside panels wired wye-style), the formula divides by 3 times volts times power factor. Mixing these two up is the single most common three-phase calculation error: the line-to-line and line-to-neutral results for the same load are noticeably different numbers, not interchangeable.
Going the other direction, amps to watts, is the same relationship solved for power instead of current: multiply amps by volts (and by power factor, for AC) rather than dividing. Switch the direction below to convert either way with the same inputs.
DC: A = W / V | AC single-phase: A = W / (V × PF) | AC three-phase line-to-line: A = W / (√3 × V × PF) | AC three-phase line-to-neutral: A = W / (3 × V × PF) | Reverse (amps to watts): multiply instead of divide, e.g. W = A × V × PF- wattsW1500Real power drawn by the load, in watts, usually the number printed on an appliance, motor, or device nameplate.
- voltsV120Supply voltage. For three-phase, this is either the line-to-line or line-to-neutral voltage depending on which circuit type is selected.
- powerFactorratio1The ratio of real power to apparent power, from 0 to 1. Purely resistive loads (heaters, incandescent lighting) use 1; motors and most electronics typically run 0.8 to 0.95.
- ampsAThe resulting current draw, in amps, that the circuit or conductor actually needs to carry.
- watts
- W
- Real power drawn by the load, in watts, usually the number printed on an appliance, motor, or device nameplate.
- volts
- V
- Supply voltage. For three-phase, this is either the line-to-line or line-to-neutral voltage depending on which circuit type is selected.
- powerFactor
- ratio
- The ratio of real power to apparent power, from 0 to 1. Purely resistive loads (heaters, incandescent lighting) use 1; motors and most electronics typically run 0.8 to 0.95.
- amps
- A
- The resulting current draw, in amps, that the circuit or conductor actually needs to carry.
Using the Watts to Amps Calculator
Enter convert
Choose from Watts to amps, Amps to watts.
Enter circuit type
Choose from AC, single-phase, DC (direct current), AC, three-phase (line-to-line voltage), AC, three-phase (line-to-neutral voltage).
Enter powerW
Type the figure you already have, then press Calculate.
Enter currentA
Type the figure you already have, then press Calculate.
Enter voltageV
Type the figure you already have, then press Calculate.
Enter power factor (ignored for dc; use 1 for a purely resistive load)
Any value between 0.01 and 1.
Read the result
Press Calculate to update the result. Until you do, the last result is dimmed and marked as out of date, so you always know which numbers belong to the values in the boxes.
A Real Worked Example
A 1500-watt space heater plugged into a standard 120-volt household circuit at a power factor of 1 (space heaters are purely resistive) draws 1500 / (120 × 1) = 12.5 amps. That number matters beyond curiosity: a typical household circuit is protected by a 15-amp or 20-amp breaker, and the National Electrical Code caps a continuous load, anything running 3 or more hours, at 80% of the breaker's rating. On a 15-amp breaker, that ceiling is 12 amps, so this heater alone would trip a 15-amp circuit if run continuously, and it leaves no real margin even on a 20-amp circuit once anything else shares that circuit.
Swap the same load onto 240 volts instead and the draw is cut in half, 1500 / (240 × 1) = 6.25 amps, which is exactly why higher-draw appliances (dryers, ranges, water heaters) are wired at 240 volts rather than 120: the same power moves through the wire at roughly half the current, letting it use a lighter conductor safely. For more on why the 80% figure exists at all, see the continuous-load guidance below.
DC circuit example
A 100-watt DC load on a 12-volt system, a common solar, RV, or automotive setup, draws 100 / 12 = 8.33 amps. There's no power factor in this calculation at all: DC has no reactive component, so real power and apparent power are the same thing. This is also why undersized wire is a bigger risk on 12V DC systems than it looks: the same 100 watts that draws about 0.83 amps at 120V AC draws ten times that current at 12V, which is exactly why solar and RV wiring guides call for much heavier gauge wire than household AC wiring carrying the same wattage.
AC three-phase example (line-to-line voltage)
A 10,000-watt three-phase load on a 208V line-to-line system at a 0.9 power factor, typical of a mid-size commercial HVAC compressor, draws 10000 / (1.732 × 208 × 0.9) = 30.84 amps. That 208V figure is the number printed on the equipment's own nameplate in the vast majority of commercial installs, since line-to-line is what's normally specified for three-phase gear, which makes this the formula worth double-checking against a nameplate before assuming the line-to-neutral version applies instead.
AC three-phase example (line-to-neutral voltage)
The same 10,000-watt load measured from one hot leg to neutral instead, 120V on a 208Y/120 system at the same 0.9 power factor, draws 10000 / (3 × 120 × 0.9) = 30.86 amps: within a fraction of an amp of the line-to-line result above, because both describe current flowing through the same real load on the same underlying system. The near-identical answer isn't a coincidence particular to these numbers; it holds whenever the line-to-line and line-to-neutral voltages actually belong to the same wye system, which is the whole reason both formulas exist.
Amps to watts example (reverse direction)
Running the primary example above in reverse: a device pulling 12.5 amps on a 120-volt single-phase circuit at a power factor of 1 is drawing 12.5 × 120 × 1 = 1500 watts. This is the same equation as the watts-to-amps direction, solved for power instead of current, which is why a clamp meter reading (amps) and a nameplate rating (watts) for the same device should always convert back to each other exactly, given the same voltage and power factor.
What Else to Know
Power Factor: The Detail Most Watts-to-Amps Conversions Skip
Watt's law itself, current equals power divided by voltage, is simple enough that a calculator barely seems necessary. What actually trips people up converting watts to amps for a real device is power factor, and skipping it is the most common reason a hand calculation and a clamp meter reading disagree.
Power factor exists because alternating current has two components: real power (measured in watts, the part that actually heats, lights, or spins something) and reactive power (created by the magnetic fields inside motors, transformers, and compressors, which does no useful work but still has to be delivered). Apparent power, measured in volt-amps, is the combination of both, and it's apparent power, not real power, that actually determines how much current a wire carries. Power factor is the ratio between them: real power divided by apparent power, always between 0 and 1.
A purely resistive load, an incandescent bulb, a space heater, a toaster, has a power factor of 1: all the delivered power is real power, so amps equal watts divided by volts with nothing else in the equation. An induction motor, a refrigerator compressor, an air conditioner, or a fluorescent or older LED driver with a cheap ballast typically runs 0.8 to 0.95, meaning it draws more current than its wattage rating alone would suggest. A 1000-watt motor at 0.85 power factor and 120 volts draws 1000 / (120 × 0.85), about 9.8 amps, versus 8.33 amps if power factor were ignored entirely, a 17% understatement that can be the difference between a wire sized correctly and one running hotter than its rating allows.
When an appliance nameplate lists amps directly, use that number. When it lists only watts and you need amps for wiring or breaker sizing, and the device has a motor or compressor, 0.8 to 0.9 is a reasonable default in the absence of a manufacturer-specified value; for straightforward resistive heating elements, 1 is correct and exact.
Single-Phase vs Three-Phase: Line-to-Line and Line-to-Neutral Amps
Most homes run on single-phase AC power, one sine wave, one pair of hot and neutral wires (plus ground), which is why the plain A = W / (V x PF) formula covers nearly every household watts-to-amps question. Three-phase power, standard in commercial buildings, industrial equipment, and larger motors, uses three separate sine waves offset by 120 degrees from each other, and that structure changes the math in a way that catches people who assume it's just the single-phase formula with a bigger number.
The first fork is which voltage was actually measured. Line-to-line voltage (sometimes written L-L or phase-to-phase) is measured between any two of the three hot conductors, and it's the number printed on most three-phase motor and equipment nameplates: 208V, 240V, 400V, and 480V are common line-to-line ratings in North America. Line-to-neutral voltage (L-N) is measured between one hot conductor and the system neutral, and in a standard wye-configured system it equals the line-to-line voltage divided by the square root of 3, roughly 1.732; a 208V line-to-line system has a 120V line-to-neutral voltage, and a 480V line-to-line system has a 277V line-to-neutral voltage.
Using line-to-line voltage, the formula is A = W / (√3 x V x PF). Using line-to-neutral voltage instead, it's A = W / (3 x V x PF); the 3 replaces the square-root-of-3 because a line-to-neutral calculation is really a per-phase calculation multiplied out across all three phases.
Put the same 10,000-watt three-phase load through both: at 208V line-to-line and 0.9 power factor, that's 10000 / (1.732 × 208 × 0.9), about 30.84 amps. At 120V line-to-neutral and the same power factor, it's 10000 / (3 × 120 × 0.9), about 30.86 amps, close to the first result here because 208V line-to-line and 120V line-to-neutral describe the same underlying 208Y/120 system; the two formulas exist precisely so either voltage measurement lands on the correct current for that same real load. Using the wrong formula for the voltage actually measured, rather than mixing up which system it is, is the error worth double-checking before trusting a three-phase result.
Reading Real Wattage Off an Appliance or Motor Nameplate
Converting watts to amps is only as accurate as the wattage figure going in, and nameplates are not always as literal as they look. A device's nameplate wattage is typically its rated maximum continuous draw under normal operating conditions, not necessarily what it pulls at every moment: a refrigerator compressor cycles on and off rather than running continuously at its rated wattage, and many motors draw a brief inrush current several times their running current at the instant they start, which the steady-state watts-to-amps formula does not capture.
When a nameplate lists amps directly rather than watts, use the listed amps: it already reflects the manufacturer's own measured or rated current, including whatever power factor and inefficiency the actual hardware has, and back-calculating watts from voltage and an assumed power factor introduces error a direct reading doesn't have. When only watts and voltage are listed, this calculator's DC and AC single-phase formulas apply directly for most household electronics and single-phase appliances; check whether the device is resistive (heating, lighting) or has a motor or compressor before assuming a power factor of 1. More math and unit-conversion tools on CalculatorPlanet cover a wide range of everyday conversions if a different calculation is needed next.
For motors specifically, nameplate data usually includes full-load amps (FLA) directly, which is the number to use for wiring and breaker sizing rather than recalculating from horsepower or wattage; the National Electrical Code's own motor tables (NEC Table 430.250 and related tables) are the authoritative source when a nameplate is missing or illegible, and they already build in typical efficiency and power factor for standard motor types.
Why the Calculated Amps Isn't the Whole Sizing Picture
A watts-to-amps result gives the actual current a load draws under normal operation, but sizing a circuit, breaker, or conductor around that number alone is how circuits end up nuisance-tripping or, worse, overheating. Two adjustments matter beyond the raw calculation.

First, the National Electrical Code (NFPA 70) requires that a continuous load, defined as one expected to run at maximum current for 3 hours or more, be sized at no more than 80% of a breaker's or conductor's rating, which is the same as saying the breaker or wire must be rated for at least 125% of the calculated continuous amps. A 16-amp continuous load needs at least a 20-amp breaker (16 / 0.8 = 20), and the same 125% math applies at any load: a 12-amp continuous load still needs a 15-amp breaker, not exactly a 12-amp one, to leave the required headroom.
This margin exists because sustained near-maximum current heats a breaker and conductor more than the same current running briefly, and the code's ampacity tables already assume that headroom is present.
Second, calculated amps assumes ideal conditions: a single circuit, unrestricted airflow around the conductor, and no unusual ambient heat. Multiple current-carrying conductors bundled in the same conduit, high ambient temperatures (an attic run in summer, proximity to a furnace), and long conductor runs where voltage drop becomes significant all reduce a wire's safe ampacity below its plain rated value, which is why the NEC's conductor ampacity tables include separate derating factors for exactly these situations rather than a single number per wire gauge.
None of this changes what this calculator returns, the real current a load draws, but it's the difference between a technically correct amps figure and a circuit, breaker, and wire gauge that's actually safe to install. For anything feeding a permanent circuit rather than a plug-in device, that sizing step belongs to a licensed electrician working from the NEC directly, not from a wattage label alone.
Reference Tables
| Watts | Amps at 120V | Amps at 240V |
|---|---|---|
| 100 W | 0.83 A | 0.42 A |
| 250 W | 2.08 A | 1.04 A |
| 500 W | 4.17 A | 2.08 A |
| 750 W | 6.25 A | 3.13 A |
| 1000 W | 8.33 A | 4.17 A |
| 1200 W | 10.00 A | 5.00 A |
| 1500 W | 12.50 A | 6.25 A |
| 1800 W | 15.00 A | 7.50 A |
| 2000 W | 16.67 A | 8.33 A |
| 2500 W | 20.83 A | 10.42 A |
| 3000 W | 25.00 A | 12.50 A |
| Watts | Amps at 220V |
|---|---|
| 200 W | 0.91 A |
| 1000 W | 4.55 A |
| 2000 W | 9.09 A |
| 3000 W | 13.64 A |
| Circuit type | Voltage used | Power factor | Formula | Result |
|---|---|---|---|---|
| DC | 120 V | n/a | A = W / V | 83.33 A |
| AC, single-phase | 120 V | 0.9 | A = W / (V x PF) | 92.59 A |
| AC, three-phase (line-to-line) | 208 V | 0.9 | A = W / (√3 x V x PF) | 30.84 A |
| AC, three-phase (line-to-neutral) | 120 V | 0.9 | A = W / (3 x V x PF) | 30.86 A |
| Amps | Watts at 120V | Watts at 240V | Watts at 220V |
|---|---|---|---|
| 1 A | 120 W | 240 W | 220 W |
| 5 A | 600 W | 1,200 W | 1,100 W |
| 10 A | 1,200 W | 2,400 W | 2,200 W |
| 15 A | 1,800 W | 3,600 W | 3,300 W |
| 20 A | 2,400 W | 4,800 W | 4,400 W |
| 25 A | 3,000 W | 6,000 W | 5,500 W |
| 30 A | 3,600 W | 7,200 W | 6,600 W |
| 40 A | 4,800 W | 9,600 W | 8,800 W |
Frequently Asked Questions About the Watts to Amps Calculator
How many amps is 1500 watts?
It depends on voltage and power factor. At 120 volts with a power factor of 1 (a purely resistive load like a space heater), 1500 watts draws 12.5 amps. At 240 volts, the same 1500 watts draws only 6.25 amps, because current drops as voltage rises for a fixed power. If the load has a motor or compressor with a power factor below 1, the real current is somewhat higher than either figure.
How do you convert watts to amps?
Divide watts by voltage for a DC circuit. For AC single-phase, divide watts by voltage times power factor. Three-phase adds one more step: divide by the square root of 3 times voltage times power factor when using line-to-line voltage, or by 3 times voltage times power factor when using line-to-neutral voltage. Power factor is 1 for resistive loads and typically 0.8 to 0.95 for motors and compressors.
What is the formula for watts to amps?
The base relationship is Watt's law: amps equal watts divided by volts. That exact form applies to DC circuits. AC single-phase inserts power factor: A = W / (V x PF). Three-phase circuits divide by either the square root of 3 or by 3, depending on whether the voltage used is line-to-line or line-to-neutral, both also multiplied by power factor.
How many amps is 2000 watts at 220V?
At 220 volts with a power factor of 1, 2000 watts draws about 9.09 amps (2000 divided by 220). This voltage is standard in much of Europe, Asia, Africa, and parts of South America, unlike the 120V and 240V figures more common in North American households. If the 2000-watt device has a motor rather than being purely resistive, expect a slightly higher real current due to power factor.
Why does power factor matter when converting watts to amps?
Power factor accounts for the gap between real power (watts, the part doing useful work) and apparent power (volt-amps, what the circuit actually has to supply). A purely resistive load has a power factor of 1, so watts and volt-amps match and the plain formula is exact. A motor or compressor typically runs 0.8 to 0.95, meaning it draws noticeably more current than its wattage alone suggests, which matters for wire and breaker sizing.
Is watts to amps the same for AC and DC?
No. DC current is simply watts divided by volts, with nothing else involved. AC current adds power factor because alternating current has both real and reactive components, so the same wattage and voltage produce a different current on AC than on DC unless the AC load happens to be purely resistive with a power factor of exactly 1, in which case the two calculations do match.
What's the difference between line-to-line and line-to-neutral in three-phase?
Line-to-line voltage is measured between any two of the three hot conductors and is the number usually printed on three-phase equipment nameplates. Line-to-neutral voltage is measured between one hot conductor and the system neutral, and in a standard wye system equals line-to-line voltage divided by the square root of 3. Each uses a different amps formula, so using the wrong one for the voltage actually measured gives an incorrect current.
How many amps does a 1000 watt appliance draw?
At 120 volts and a power factor of 1, a 1000-watt appliance draws 8.33 amps. At 240 volts, the same appliance draws 4.17 amps. At 220 volts, common outside North America, it draws about 4.55 amps. These figures assume a purely resistive load; a 1000-watt device with a motor typically draws somewhat more current once its actual power factor is accounted for.
Can I use a 15-amp breaker for a 1500-watt load?
Not safely if the load runs continuously. A 1500-watt load at 120 volts draws 12.5 amps, and the National Electrical Code caps a continuous load (running 3 or more hours) at 80% of a breaker's rating, which is 12 amps for a 15-amp breaker. A 12.5-amp continuous draw exceeds that margin, so a 20-amp breaker and appropriately rated wiring are the safer, code-correct choice.
How many amps is 3000 watts at 120V?
At 120 volts with a power factor of 1, 3000 watts draws 25 amps, which exceeds what a standard 20-amp or even 30-amp North American branch circuit is typically designed to carry continuously without derating. Loads this size, large space heaters, electric water heaters, and similar appliances, are commonly wired at 240 volts instead, where the same 3000 watts draws only 12.5 amps.
Do I need power factor for a home watts-to-amps conversion?
For most single household appliances with a resistive heating element, a power factor of 1 is accurate and no adjustment is needed. For motor-driven appliances, refrigerators, air conditioners, and pumps, an assumed power factor of 0.8 to 0.9 gives a closer estimate than ignoring it, though the nameplate's own listed amps, when present, is always more accurate than any calculated figure.
What voltage should I use for a three-phase motor's nameplate watts?
Use whichever voltage the nameplate itself specifies, since that determines which formula applies. Most three-phase motor nameplates list line-to-line voltage (such as 208V, 240V, or 480V), which uses the square-root-of-3 formula. If a nameplate specifically states a line-to-neutral voltage instead, which is less common, use the line-to-neutral formula that divides by 3 rather than by the square root of 3.
How many watts is 1 amp?
It depends entirely on voltage, since watts equal amps multiplied by volts. At 120 volts, 1 amp is 120 watts. At 240 volts, 1 amp is 240 watts. At 220 volts, common outside North America, 1 amp is 220 watts. For an AC motor or other load with a power factor below 1, multiply by that power factor too, which lowers the wattage slightly below the plain amps-times-volts figure.
What is 20 amps in watts?
At 120 volts and a power factor of 1, 20 amps is 2,400 watts (20 × 120). At 240 volts, the same 20 amps is 4,800 watts, since watts scale directly with voltage for a fixed current. This is why a 20-amp breaker is rated for meaningfully more load on a 240-volt circuit than on a 120-volt one, even though the amp rating on the breaker itself is identical.
How many watts is 10 amps at 220 volts?
10 amps at 220 volts and a power factor of 1 is 2,200 watts (10 × 220). 220 volts is the standard household voltage across most of Europe, Asia, and Africa, which is why this figure differs from the 2,400-watt result the same 10 amps would give at North America's 240-volt standard. Multiply by a lower power factor for a motor or compressor load, which reduces the real wattage slightly.
How many watts is 240 amps?
240 amps is an unusually large current for household wiring, and almost always shows up in a 12-volt or 24-volt DC context instead, such as a solar battery bank, marine electrical system, or heavy-duty winch draw. At 12 volts DC, 240 amps is 2,880 watts (240 × 12). At 24 volts DC, the same 240 amps is 5,760 watts, which is why higher-voltage battery banks are used for large loads: less current for the same power, and a lighter cable.
References
- [1] National Fire Protection Association. “NFPA 70, National Electrical Code.” NFPA. Accessed 2026-09-27.
- [2] U.S. Department of Energy. “Estimating Appliance and Home Electronic Energy Use.” Energy.gov, Office of Energy Efficiency & Renewable Energy. Accessed 2026-09-27.
Related calculators
- Amps to Kilowatts CalculatorConvert amps to kilowatts for DC, single-phase and three-phase circuits, with power factor, kVA, kWh per day or month and an optional energy cost.Open
- Binomial Distribution CalculatorBinomial distribution calculator. Enter trials, success probability and successes for exact, at most, at least and between probabilities, plus mean.Open
- Box Plot CalculatorBox plot calculator with steps: get Q1, median, Q3, whiskers, fences and outliers from data or five numbers, with a text box and whisker plot.Open
- Boyle's Law CalculatorBoyle's law calculator: solve P1 V1 = P2 V2 for pressure or volume in atm, kPa, bar, mmHg, psi, L, mL or m3, with gauge pressure and examples.Open